Pool Dose Lab

Pool Heater Size Calculator

Enter your pool's surface area, volume and temperatures to get the heater size in BTU/hr, the gas or electricity needed to warm the water, and how many hours your heater will take.

Last reviewed · How we calculate

Your pool

Not sure? Work it out from your pool's size.

Length × width; 16 × 32 ft = 512.

Temperatures (°F)
Heater and energy prices
Heater you have or are considering

US minimum for new gas pool heaters is 82%.

Example — use your bill. Propane: about 0.92 therm per gallon.

DOE: usually 3.0 to 7.0.

Example — use your bill.

Your result

—

Gas heater size (input)
—
Heat-up rise
—
Energy to heat the water
—
Output for your heat-up time
—
Gas for the heat-up
—
Heat pump for the heat-up
—
Time with your heater
—

Heat-up figures ignore heat lost from the surface while heating, so real times and costs are higher — often much higher on a cool, windy night without a cover.

How the pool heater size calculator works

A pool heater has two jobs: bring cold water up to temperature, and then keep it there while the surface loses heat to the air. A pool heater size calculator should cover both. This one sizes the heater for the second job using the US Department of Energy's published method, which is also how a pool heat pump calculator should size a heat pump, and then estimates the energy, cost and time for the first job.

Heater output (BTU/hr) = surface area (sq ft) × (desired water °F − average air °F of coldest month) × 12 Energy to heat the water (BTU) = gallons × 8.345 × degrees of rise Gas: therms = BTU ÷ efficiency ÷ 100,000 Heat pump: kWh = BTU ÷ 3,412 ÷ COP Time (hours) ≥ BTU needed ÷ heater output

The DOE notes that its factor of 12 assumes a temperature rise of 1 to 1¼ °F per hour and an average wind of 3½ mph at the pool surface. If you want a faster rise, the DOE suggests multiplying the result by 1.5 for 1.5 °F per hour or by 2 for 2 °F per hour. It also recommends having a trained pool professional do the final sizing, since wind exposure, shade and covers change the answer.

Worked example: 16 × 32 ft pool at 82 °F

The pool's surface is 512 sq ft and holds 15,000 gallons. You want 82 °F water, and the coldest month you plan to swim averages 60 °F, so the rise is 22 °F. Heater output: 512 × 22 × 12 = 135,168 BTU/hr. A gas heater at 82% efficiency would need an input rating of at least about 165,000 BTU/hr, and gas heaters are labeled by input, so a 200,000 BTU/hr or larger unit fits with margin. A heat pump is labeled by output, so you would look for one rated at 135,000 BTU/hr or more at cool-air conditions.

Now the first warm-up from 65 °F. Raising 15,000 gallons by 17 °F takes 15,000 × 8.345 × 17 = about 2.13 million BTU. A 400,000 BTU/hr gas heater at 82% delivers about 328,000 BTU/hr, so it needs at least 6.5 hours (about 2.6 °F per hour) and burns about 26 therms — $38.93 at $1.50 per therm. A 110,000 BTU/hr heat pump with a COP of 5 needs at least 19.3 hours and uses about 125 kWh — $21.20 at $0.17 per kWh. These are lower bounds; the surface keeps losing heat while you heat.

Reference: heater output by surface area

DOE sizing, BTU/hr output (area × rise × 12)
Surface area10 °F rise15 °F rise20 °F rise25 °F rise
300 sq ft36,00054,00072,00090,000
400 sq ft48,00072,00096,000120,000
512 sq ft (16 × 32)61,44092,160122,880153,600
600 sq ft72,000108,000144,000180,000
800 sq ft96,000144,000192,000240,000
Energy to raise the water 10 °F (no losses)
Pool sizeBTUGas therms at 82%Heat pump kWh at COP 5
10,000 gal834,50010.249
15,000 gal1,251,75015.373
20,000 gal1,669,00020.498
25,000 gal2,086,25025.4122

Gas heater or heat pump?

Gas heaters (natural gas or propane) heat fast regardless of air temperature, which suits pools heated occasionally — a weekend, a party — and cool shoulder seasons. Since April 16, 2013, new gas pool heaters sold in the US must have a thermal efficiency of at least 82% — at least 82% of the fuel's energy must end up as heat in the water. Heat pumps move heat from the air into the water. The DOE puts typical COPs at 3.0 to 7.0, meaning 3 to 7 units of heat per unit of electricity, which makes them much cheaper per degree when the air is mild. Their output drops as the air cools, and they heat slowly, so they suit pools kept warm all season rather than heated on demand.

Common sizing mistakes

  • Using the summer average instead of the coldest month you want to swim. A heater sized for July will struggle in May.
  • Comparing a gas heater's input rating with a heat pump's output rating. Multiply gas input by efficiency first.
  • Ignoring flow. Heaters need a minimum flow to fire; check it against your pump size calculation, especially if you slow a variable-speed pump.
  • Skipping the cover. The DOE's guidance on pool covers says heating savings of 50–70% are possible, so a cover often matters more than an extra 100,000 BTU.

Gas heaters need correct venting, clearances and gas line sizing. Have a licensed installer handle gas and electrical connections, and never run a heater with low flow or a dirty filter.

Heat and the rest of your pool

Warm water evaporates faster, so expect higher top-up needs — the pool evaporation calculator estimates them. Warmer water also uses chlorine faster and pushes the calcium saturation index up, so test more often after a heat-up. If you also run a spa, the hot tub electricity cost calculator handles the smaller, hotter volume.

Questions people ask

What size heater do I need for my pool?

The US Department of Energy method multiplies surface area by the temperature rise (desired water temperature minus the average air temperature of the coldest month you swim) by 12. A 16 × 32 ft pool (512 sq ft) kept at 82 °F with 60 °F average air needs about 135,168 BTU/hr of heater output.

How long does it take to heat a pool?

Raising 15,000 gallons by 17 °F takes about 2.13 million BTU. A 400,000 BTU gas heater at 82% efficiency delivers about 328,000 BTU/hr and needs at least 6.5 hours; a 110,000 BTU heat pump needs at least 19.3 hours. Heat lost from the surface during heating adds to both, especially without a cover.

How do I size a pool heat pump?

Use the same DOE output figure (area × temperature rise × 12) and compare it with the heat pump's rated output in BTU/hr at conditions close to yours. Heat pump output falls as air temperature drops, so check the rating at a cooler air temperature if you plan to swim in spring or fall.

How much does it cost to heat a pool with gas vs a heat pump?

Heating 15,000 gallons by 17 °F takes about 26 therms of gas at 82% efficiency ($38.93 at $1.50 per therm) or about 125 kWh with a heat pump at COP 5 ($21.20 at $0.17 per kWh). Your prices and the heat lost during heating change the totals.

How many BTUs does it take to heat a pool 1 degree?

One gallon of water needs about 8.345 BTU per °F, so 1,000 gallons needs about 8,345 BTU and a 15,000 gallon pool about 125,175 BTU per degree, before any heat loss.